Bradford White Corp Water Heater Solar Water Heater with Electric Backup User Manual

Solar Water Heater With Electric Backup  
Solar Saver® Heaters  
SERVICE  
MANUAL  
Troubleshooting Guide  
and Instructions for Service  
(To be performed ONLY by  
qualified service providers)  
Models Covered  
by This Manual:  
S-SW2-60R6DS  
S-SW2-75R6DS  
S-SW2-115R6DS  
Manual 238-47297-00A  
Save this manual for future reference  
 
GENERAL INFORMATION  
Commonly Used Formulas  
Single Phase Amps = Watts Example 4500W/240V = 18.75A  
Volts  
Watts = Amps x Volts  
Example 18.75A x 240V = 4500W  
2
Ohms = Volts2  
Watts  
Example (240V) / 4500W = 12.8 Ohms  
Service Wire Configuration  
240 VOLT  
BLACK  
GREEN  
RED  
Grounding  
Ungrounded  
Ungrounded  
240  
120  
120  
Wattage Limitation at 240 Volts  
Solar Water Heater with Double Electric Element Backup Series (Non-Simultaneous operation)  
Maximum  
Wattage  
Element  
Upper/Lower  
5,500/5,500  
5,500  
3
 
GENERAL INFORMATION  
Surface Mounted Thermostats  
Surface mounted thermostats are mounted into a bracket which holds the thermostat against the side of the tank.  
Surface mounted thermostats respond to tank surface temperatures to sense a call for heat, set point temperature  
settings and high limit (ECO) activation. It is important that the entire back surface of the thermostat is in full contact or  
flush with the tank. Improperly mounted thermostat will lead to improper heater operation.  
Manual  
ECO (high limit)  
Reset button  
Temperature  
control Dial  
Upper thermostat  
Surface Mount  
With  
ECO (high limit)  
89T Series  
Lower thermostat  
Surface Mount  
59T Series  
Direct Immersion “Screw-in” Type Heating Element  
1-½ Hex  
Screw-in Flange  
Terminal Block  
Zinc Incoloy Sheath  
Terminal Block  
Screw  
Element Rating Ink Stamped  
on side of Terminal Block.  
4
 
SEQUENCE OF OPERATION  
Non-Simultaneous Operation  
Non-Simultaneous Mode: Allows only one heating element to operate at a time. For example, when the tank is cold,  
the upper element is energized first, heating the top of the tank. Only when the upper thermostat is satisfied, the upper  
element is de-energized and power is directed to the lower thermostat, energizing the lower element and heating the  
bottom portion of the tank until the lower thermostat is satisfied. As hot water is drawn off the tank, it is replaced with  
cold water delivered through the dip tube to the bottom of the tank. When the tank cools at the lower thermostat level,  
the thermostat will call for heat energizing the lower element. If enough hot water is drawn from the tank, the top portion  
of the tank cools and the upper thermostat will call for heat, de-energizing the lower element and allowing only the top  
element to energize until the upper thermostat is satisfied.  
The lower thermostat in the solar water heater is located above the internal heat exchanger. This design allows the heat  
exchanger to be in cooler water during short draws, providing more heat transfer from the solar heating system.  
Solar water heaters with double electric element backup are designed to operate using a single operating mode detailed  
as follows:  
Sequence of Operation- Double Element, Non-Simultaneous Operation, Single Phase.  
1
Line voltage is applied across terminals  
L1 & L3 of the upper thermostat. ECO is  
closed, so there is voltage at terminal L4  
and to one side of the upper and lower  
elements.  
1
2
2
Tank is cold. Therefore, the thermostats are closed  
at terminals T2 & 2 (calling for heat). The circuit is  
complete through the upper thermostat only,  
ECO  
Closed  
Thermostat closed  
at terminal T2  
allowing current to flow through the upper element.  
Upper  
T’stat  
Upper  
T’stat  
When the upper thermostat is satisfied, it opens at  
terminal T2, interrupting current flow through the  
upper element. Terminal T4 closes, allowing voltage  
to pass to terminal 1 of the lower thermostat. This  
completes the circuit through the lower thermostat  
and allows current flow through the lower element.  
3
Upper  
Element  
Upper  
Element  
Thermostat closed  
at terminal 2  
Lower  
T’stat  
Lower  
T’stat  
4
5
When the lower thermostat is satisfied, it opens at  
terminal 2, interrupting current flow through the  
lower element. The system is now in stand-by mode  
waiting for the next call for heat  
Lower  
Lower  
Element  
Element  
The lower thermostat/element  
combination will generally  
3
4
5
cycle on and off more often  
then the upper. In some cases,  
such as a cold tank or in high  
demand periods, the  
Thermostat closed  
Thermostat closed  
upper thermostat will  
at terminal T4  
at terminal T2  
call for heat (opening at  
Upper  
T’stat  
Upper  
T’stat  
Upper  
T’stat  
terminal T4 and closing at  
terminal T2) prior to the lower  
thermostat being satisfied. This  
will interrupt current flow  
Upper  
Element  
Upper  
Upper  
Element  
through the lower thermostat  
Element  
and element and allow current  
to flow through the upper  
Thermostat open  
between terminals  
1 and 2  
Thermostat closed  
between terminals  
1 and 2  
element only. When the upper  
Lower  
T’stat  
Lower  
T’stat  
Lower  
T’stat  
thermostat is satisfied, it  
resumes operation as  
Lower  
Element  
described in sequence #3  
Lower  
Element  
Lower  
Element  
above.  
5
 
TROUBLESHOOTING  
NOTICE  
This Service Manual is for servicing the solar water heater. If other components of an  
installed system requires service, those questions should be directed to the installer or  
the specific component manufacturer.  
Most common cause for improper electric backup operation can be linked to heating element failure.  
When troubleshooting an electric backup solar water heater with the incidence of “No Hot Water” or “Insufficient Amount  
of Hot Water”, it’s always a good idea to check the heating elements first following the procedure on page 9.  
Common Heating Element Failures Are:  
1. Dry Firing. Element may be partially submerged in water or most likely, completely exposed with no water in  
the tank. In some cases sediment or lime build up around an element can eventually cause an air pocket, and  
within seconds, result in a dry-fired element. At this point the element becomes inoperative. When element  
replacement is required, be sure the tank is full of water prior to energizing the water heater.  
2. Grounded Element. An element with a short circuit to ground will in most cases cause the circuit breaker in  
the service panel to open or shut off. In some cases there may not be enough current draw for the circuit  
breaker to open. This will allow the heating element to be in continuous operation resulting in over-heated  
water, limited only by the ECO (Energy Cut Off) located in the thermostat. Repeated actuation of the ECO  
reset button on the thermostat usually is the result of a grounded element.  
3. Sediment build up. Slow hot water recovery can usually be traced back to sediment or lime build up around  
the heating element. Sediment build up can also over time cause a dry-fired element.  
Illustration 1, below shows a common “Screw-In” type heating element identifying certain features commonly referred  
to throughout this manual.  
1-½ Hex  
Screw-in Flange  
Terminal Block  
Zinc Plated Incoloy Sheath  
Terminal Block  
Screw  
Element Rating Ink Stamped  
on side of Terminal Block.  
Illustration 1  
Typical Direct Immersion “Screw-In”  
Type Heating Element  
6
 
TROUBLESHOOTING  
WARNING  
Quick Step Plan to Hot Water  
1. TURN OFF power to water heater and solar controller.  
Check all wire connections to insure they are tight and  
corrosion free.  
High voltage exposure. Use caution when  
making voltage checks to avoid personal injury.  
NOTICE  
This Service Manual is for servicing the solar water heater.  
If other components of an installed system requires  
service, those questions should be directed to the installer  
or the specific component manufacturer.  
2. Turn power “ON” and determine that service voltage is  
present and the high limit (ECO) has not actuated  
(see procedure on page 8).  
3. Check for inoperative heating element (see procedure on page 9).  
4. Check for proper thermostat operation (see procedures beginning on page 10). NOTE: Thermostat testing procedures  
assume items 2 and 3 above are in working order.  
SERVICE  
CORRECTIVE ACTION  
SYMPTOM  
PROBABLE CAUSE  
PROCEDURE  
3. See Service Procedure  
RE-II, Page 9.  
4. See Service Procedure  
RE-III, Page 10.  
5. See Service Procedure  
RE-I, Page 8.  
6. Refer to Controller  
manufacturer  
1. No Power to heater.  
2. Loose wire connections.  
3. Inoperative upper heating element.  
4. Inoperative upper thermostat.  
5. Open ECO.  
6. Inoperative solar controller or  
connection.  
1. Check fuses or circuit breakers in service panel.  
2. Check all wire connections.  
3. Check heating elements. Replace as needed.  
4. Check thermostats operation. Replace as  
needed.  
5. Check ECO. Reset or replace thermostats as  
needed.  
6. Check for proper solar controller operation.  
7. Check for proper circulator operation.  
No Hot Water  
7. Inoperative circulator in solar heating  
system.  
7. Refer to circulator  
manufacturer  
1. Check heating elements, replace as needed.  
2. Increase thermostat setting.  
3. Check thermostats, replace as needed.  
4. Check all wire connection.  
5. Remove heating elements and check for lime  
build up.  
1. Inoperative lower heating element.  
2. Thermostats set to low.  
1. See Service Procedure  
RE-II, Page 9.  
3. See Service Procedure  
RE-III, Page 10.  
5. See Service Procedure  
RE-V, Page 13.  
10. See Service Procedure  
RE-VI, Page 14.  
3. Inoperative thermostats.  
4. Loose wire connection.  
5. Sediment or lime build up on elements.  
6. High demand period.  
Not Enough Hot  
Water  
6. Reduce demand.  
7. Undersized heater.  
7. Replace with larger heater.  
8. Temper water to heater.  
9. Correct plumbing connections.  
10. Check dip tube, replace as needed.  
11. Review solar collector calculations and  
orientation.  
8. Very cold inlet water to heater.  
9. Plumbing connections reversed.  
10. Damaged dip tube.  
11. Refer to solar collector  
manufacturer.  
11. Improper solar collector application.  
1. Remove heating elements and check for  
lime build up.  
1. Sediment or lime build up on elements.  
2. Loose wire connections.  
1. See Service Procedure  
RE-V, Page 13.  
3. See Service Procedure  
RE-III, Page 10.  
Slow Hot Water  
Recovery  
2. Check all wire connections.  
3. Inoperative thermostats.  
3. Check thermostats, replace as needed.  
4. Check terminal block of element for proper  
voltage and wattage rating.  
4. Derated heating element installed.  
1. See Service Procedure  
RE-IV, Page 12.  
2. See Service Procedure  
RE-II, Page 9.  
4. See Service Procedure  
RE-III, Page 10.  
5. See Service Procedure  
RE-I, Page 8.  
1. Thermostat not in contact with tank.  
2. Grounded heating elements.  
3. Thermostat set to high.  
1. Position thermostat flush with tank surface.  
2. Check heating elements. Replace as needed.  
3. Adjust thermostats to desired setting.  
4. Check thermostats, replace as needed.  
5. Check ECO, replace thermostat as needed.  
6. Replace with larger heater.  
Over Heated  
Water or  
Continues  
Operation  
4. Inoperative thermostats.  
5. Inoperative ECO.  
6. Undersized water heater.  
7. Incorrectly adjusted mixing device.  
7. Adjust mixing device.  
8. Improperly programmed solar controller. 8. Refer to solar controller instructions.  
7. Refer to included mixing  
device instructions.  
Noisy (singing or  
hissing) Elements  
1. Lime formation on elements.  
1. Remove and clean heating elements.  
Replace as needed.  
1. See Service Procedure  
RE-V, Page 13.  
7
 
SERVICE PROCEDURE RE-I  
Line Voltage & High Limit (ECO)  
Testing  
Line Voltage Testing  
WARNING  
High voltage exposure. Use caution when  
making voltage checks to avoid personal injury.  
1. Turn “OFF” power to water heater.  
2. Remove access cover(s) from front of water  
heater. Remove insulation and plastic cover  
from thermostat.  
ECO reset  
button  
3. Set multi-meter to volts AC.  
4. Turn power “ON” to water heater.  
5. Check voltage across terminals L1 & L3  
of upper thermostat (see illustration 2).  
A) Rated voltage IS present, power to the water  
heater is okay.  
B) Rated voltage NOT present, Check circuit breaker  
at service panel.  
Illustration 2  
Illustration 3  
High Limit (ECO) Testing  
1. Check voltage across terminals L1 & L4 upper thermostat (see illustration 3).  
A) Rated Voltage IS present, ECO is okay.  
B) Rated voltage NOT present, proceed to step 2.  
2. Turn power “OFF” to water heater and firmly press ECO reset button on thermostat. Turn power “ON” and recheck  
voltage across terminals L1 & L4 of upper thermostat  
(see illustration 3).  
A) Rated voltage IS present, the ECO has previously opened indicating the water in the tank, at  
some point did overheat, check the following:  
1. Thermostat must be in full contact with tank.  
2. Be sure heating elements are not shorted to ground (see page 9).  
3. Proper thermostat operation (see procedures beginning on page 10).  
B) Rated voltage NOT present, water in tank may be over heated.  
1. If water is hot, turn “OFF” power to water heater and flow water through tank to cool below set point  
of upper thermostat. Recheck voltage per step 1.  
2. If water is cool, Replace upper thermostat.  
8
 
SERVICE PROCEDURE RE-II  
Heating Element Testing  
Testing For Open Or Burned Out Element.  
WARNING  
High voltage exposure. Be sure power is turned  
OFF to water heater prior to performing this  
procedure.  
Step 1. TURN OFF POWER TO WATER HEATER.  
Step 2. Remove access covers from front of water  
heater. Remove insulation and plastic cover  
from thermostat.  
Step 3. Disconnect wires from heating element.  
Step 4. Set multi-meter to “ohms” setting.  
Step 5. Touch probes of multi-meter to screw  
terminals of heating element  
(see illustration 4).  
Meter Probe  
Step 6. Reading should be 12.8 ohms ( 6%) for a 240  
volt, 4500 watt element:  
Ohms = Volts2  
Watts  
A reading outside the range using the formula  
above ( 6%), indicates a bad element and the  
element must be replaced.  
Element Screw Terminals  
Illustration 4  
Testing For Heating Element Short Circuit To  
Ground.  
Step 1. TURN OFF POWER TO WATER HEATER.  
Step 2. Remove access covers from front of water  
heater. Remove insulation and plastic cover  
from thermostat.  
Step 3. Disconnect wires from heating element.  
Step 4. Set multi-meter to “ohms” setting.  
Element Screw Terminal  
Meter Probe  
Step 5. Touch one probe of multi-meter to either screw  
terminal of heating element and the other on  
the element flange (see illustration 5). There  
should be no reading on the ohm meter. Any  
reading indicates a grounded element and the  
element must be replaced. Repeat this step for  
the other screw terminal.  
Element Flange  
Illustration 5  
9
 
SERVICE PROCEDURE RE-III  
Thermostat Testing  
WARNING  
Double Element, Non-Simultaneous, Single Phase  
Operation.  
High voltage exposure. Use caution to avoid  
personal injury during this procedure.  
Water In Tank Is Cold With Power ON.  
1. This procedure assumes line voltage, ECO and  
elements are in working order.  
2. Turn power “ON” to water heater.  
3. Set multi-meter to “Volts AC”.  
4. Check across terminals L4 and T2 of  
upper thermostat (see illustration 6).  
A) Rated voltage NOT present,  
Recheck ECO. If ECO is okay,  
replace thermostat.  
B) Rated voltage IS present,  
proceed to next step.  
5. Check across element terminals  
(see illustration 7).  
A) Rated voltage NOT present,  
check wire connections from  
thermostat to element.  
Illustration 6  
Illustration 7  
B) Rated voltage IS present,  
Repeat element testing  
see page 9.  
Tank Does Not Deliver Enough Hot Water.  
1. This procedure assumes line voltage, ECO and  
elements are in working order.  
2. Turn power “ON” to water heater and set multi-meter to “Volts AC”.  
3. Adjust temperature setting of upper thermostat to the highest setting.  
Water temperature in tank must be below thermostat setting for this test.  
4. See illustration 6 above, check voltage across terminals L4 and T2 of upper  
thermostat.  
A) Rated voltage IS present, okay, upper thermostat is  
calling for heat. Go to step 5 below.  
B) Rated voltage NOT present, replace upper thermostat.  
5. Adjust temperature setting of upper thermostat to the minimum setting.  
Water temperature in tank must be above thermostat setting for this test.  
6. Check voltage across terminals L4 and T4 of upper thermostat  
(see illustration 8).  
A) Rated voltage NOT present, replace upper thermostat.  
Illustration 8  
B) Rated voltage IS present, thermostat is okay. Go to step 7 on next page.  
10  
 
SERVICE PROCEDURE RE-III  
Thermostat Testing  
WARNING  
Double Element, Non-Simultaneous, Single Phase  
Operation (continued).  
High voltage exposure. Use caution to avoid  
personal injury during this procedure.  
Not Enough Hot Water (continued).  
7. Check voltage across terminal L4 of upper  
thermostat and terminal 1 of lower thermostat  
(see illustration 9).  
A) Rated voltage NOT present,  
- check wire connection between thermostats.  
B) Rated voltage IS present, okay, go to step 8.  
8. Adjust lower thermostat to highest setting. Water temperature in  
tank must be below the lower thermostat setting for this test.  
9. Check voltage across terminal L4 of upper  
thermostat and terminal 2 of lower thermostat (see illustration 10).  
A) Rated voltage NOT present, replace lower thermostat.  
B) Rated voltage IS present, thermostat is ok.  
WARNING  
Be sure thermostats are reset to their original  
temperature settings as found prior to  
thermostat testing  
Illustration 9  
Water Temperature In Tank Is Above Thermostat Setting.  
1. This procedure assumes line voltage, ECO and elements are in working  
order.  
2. Adjust upper and lower thermostats to the lowest setting.  
3. Turn power “ON” to water heater and set multi-meter to “Volts AC”.  
4. Check across terminals L4 and T2 of upper thermostat  
(see illustration 6 on page 10).  
A) Rated voltage IS present, replace upper thermostat.  
B) Rated voltage NOT present, upper thermostat is okay. Go to step  
5 below.  
C) Lower than rated voltage IS present, recheck for grounded upper  
element (see page 9).  
5. Check across terminals L4 and 2 of lower thermostat (see illustration 10).  
A) Rated voltage IS present, replace lower thermostat.  
Illustration 10  
B) Rated voltage NOT present, lower thermostat is okay.  
C) Lower than rated voltage IS present, recheck for grounded lower  
element (see page 9).  
11  
 
SERVICE PROCEDURE RE-IV  
Thermostat Removal and Replacement  
Thermostat Removal  
WARNING  
High voltage exposure. Be sure power is  
“OFF” when performing this procedure.  
1. Turn power “OFF” To water heater.  
2. Remove access cover and insulation.  
3. Remove plastic thermostat protector from thermostat.  
4. Disconnect wires from thermostat terminals. It may be necessary to label wires for proper re-connection to  
new thermostat.  
5. Note thermostat temperature setting for proper setting of new thermostat.  
6. Slide thermostat upwards and out of mounting bracket.  
Thermostat Replacement  
1. Use a stiff brush to remove any debris or loose scale from tank surface where new thermostat will be installed.  
2. Slide new thermostat down into thermostat bracket until it snaps into place. IMPORTANT! Thermostat must set  
completely flat or flush to tank surface. An improperly installed thermostat will cause improper water heater  
operation.  
3. Refer to the wire diagram located on the inside of the access cover and re-connect wires to the thermostat. Be  
sure wire connections are snug and corrosion free. Do not over tighten, doing so may damage thermostat.  
4. Set thermostat to the original thermostat setting found on the old thermostat.  
5. Re-install plastic thermostat protector.  
6. Re-install insulation and access cover.  
7. Restore power to water heater and verify proper heater operation.  
Tank Surface  
Proper Thermostat mounting  
flush with tank surface  
Thermostat  
Improper Thermostat mounting.  
Thermostat not flush with tank surface  
Thermostat  
mounting  
bracket  
Front View  
Thermostat Mounting  
Side View  
Improper Thermostat  
Mounting  
Side View  
Proper Thermostat  
Mounting  
12  
 
SERVICE PROCEDURE RE-V  
Heating Element Removal  
and Replacement  
WARNING  
High voltage exposure. Be sure power is  
“OFF” when performing this procedure.  
Heating Element Removal  
1. Turn power “OFF” To water heater.  
2. Turn off cold water supply to heater. Connect hose to drain  
spigot of water heater and route to an open drain. Open  
a nearby hot water faucet to vent heater for draining. Open  
drain spigot of water heater and allow heater to drain  
to a point below the elements.  
WARNING  
Heater components and stored water may be  
HOT when performing the following steps in  
this procedure. Take necessary precaution to  
prevent personal injury.  
3. Close drain spigot and remove hose.  
4. Remove access cover and insulation.  
5. Remove plastic thermostat protector from thermostat.  
6. Disconnect wires from element terminals.  
7. Remove element from tank using 1-½ deep well socket or appropriate wrench. Unscrew element counter-clockwise to  
remove from tank.  
8. Be sure to remove old element gasket from the tank. It is not recommended to be re-used.  
Heating Element Replacement  
1. Check element terminal block for proper electrical rating. NOTE: Some elements have dual ratings, be sure to check  
all surfaces of the element terminal block (see illustration below).  
2. Apply new element gasket to the new element. Be sure gasket is seated flat against element flange without rolls or  
gaps (see illustration below).  
3. Clean any debris from element fitting on tank. Lubricate element threads as needed with thread lubricant.  
4. Thread new element clockwise into tank. Tighten element using 1-½ deep well socket or appropriate wrench. Do not  
over tighten, over tightening may damage element gasket.  
5. Reconnect wires to element, be sure wires are snug and corrosion free. Do not over tighten, doing so may damage  
terminal block.  
6. Resume water supply to heater, be sure tank is full of water and check for leaks.  
7. Re-install plastic thermostat protector.  
8. Re-install insulation and access cover.  
9. To resume operation, BE SURE TANK IS FULL OF WATER and restore power to water heater. Verify proper heater  
operation.  
Element Rating.  
Example: (4500 Watt, 240 Volt)  
Date Code  
Element Flange  
Element Gasket Seated Flat Against  
Element Flange Without Rolls or Gaps  
Terminal  
Block  
Manufacturer Identification  
13  
 
SERVICE PROCEDURE RE-VI  
Dip Tube and Anode Inspection and  
Replacement  
Dip Tube Inspection and Replacement  
WARNING  
Heater components and stored water may be HOT when performing the following steps in  
this procedure. Take necessary precaution to prevent personal injury.  
Step 1.  
Turn power “OFF” to water heater.  
Step 2.  
Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain.  
Open a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow  
heater to drain to a point below the inlet connection nipple.  
Step 3.  
Step 4.  
Step 5.  
Close drain spigot and remove hose.  
Disconnect inlet nipple from plumbing system.  
With an appropriate wrench, remove inlet nipple/dip tube from the water heater. Use caution not to damage  
nipple threads.  
Step 6.  
Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage.  
Hydro-jets located near the bottom of the dip tube should be open and free of any blockage.  
Anti-siphon hole located approximately 6" from the bottom of nipple, should be free of any blockage.  
Any damage such as cracks, restriction due to deformation or unintentional holes are not field repairable  
and the inlet nipple/dip tube must be replaced.  
Step 7.  
Step 8.  
Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into heater. Connect  
nipple to plumbing system, close spigot and remove drain hose, resume water supply and refill heater with  
water.  
To resume operation, BE SURE TANK IS FULL OF WATER and turn power “ON” to water heater.  
Anode Inspection and Replacement  
Step 1.  
Step 2.  
Turn power “OFF” to water heater.  
Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain.  
Open a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow  
heater to drain to a point below the outlet connection nipple.  
Step 3.  
Step 4.  
Step 5.  
Close drain spigot and remove hose.  
Disconnect outlet nipple from plumbing system.  
With an appropriate wrench, remove outlet nipple/anode from the water heater. Use caution not to damage  
nipple threads.  
Step 6.  
Step 7.  
Step 8.  
Visually inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is normal.  
If depletion is ½ of the original anode diameter (original diameter approximately ¾”), replacement is  
recommended. If any of the steel core of the anode is exposed, replacement is recommended.  
Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into heater. Connect  
nipple to plumbing system, close spigot and remove drain hose, resume water supply and refill heater with  
water.  
To resume operation, BE SURE HEATER IS FULL OF WATER and turn power “ON” to water heater.  
14  
 
Generic Parts List  
1. Integrated Mixing Device  
2. Hex Head Anode  
3. Junction Box Cover  
4. Cover Conduit/Ground  
5. ¾" Plug  
10. Heating Element  
11. Thermostat Mounting Bracket  
12. Thermostat w/High Limit (89T33)  
13. Element Gasket  
14. T&P Relief Valve  
6. Hot Water Outlet/Anode  
7. Cold Water Inlet Dip Tube  
8. Access Cover  
15. Lower Thermostat Protector (Small)  
16. Thermostat (59T)  
17. Brass Drain Valve  
9. Thermostat Protector (Large)  
18. Kit Dairy Barn Leg  
15  
 

Belkin Server LH 4 User Manual
Black Box Network Router 1001 User Manual
Black Decker Toaster T2200 T2450 User Manual
Bosch Appliances Flat Panel Television MON150CL User Manual
Brilliant Label Flat Panel Television 532H User Manual
Brother Home Theater Server DCP J4110DW User Manual
Brother Label Maker LN7629001 User Manual
Casio Digital Camera MA1002 B 1104 User Manual
Chicago Electric Work Light 66274 User Manual
Cisco Systems IP Phone VWCC User Manual